Pressure Breaker
HRS FUNKE provides pressure breaker solutions for the efficient energy distribution in high rise buildings when HVAC piping systems are deployed. The static head in these tall buildings, creates pressure that often exceeds acceptable load levels for condensers or room air conditioners.
The high quality and energy efficient HRS FUNKE plate heat exchangers can split the circuit in order to keep the pressure down at required level. The quality of HRS FUNKE plate heat exchangers ultimately results into safety of pumps, piping, fittings and valves by keeping smooth required pressure.
While spliting the piping structure for certain pressure requirements, it is very important not to waste cold in the cooling system. HRS FUNKE plate heat exchangers are designed to perform in such an energy efficient way that the energy loss is minimum as compared to any other conventional heat exchanger available in market.
Advantages of Plate Heat Exchangers as pressure breakers
The entire chilled water system will be designed for low pressure, for example 10 bar (150 psig). This means cost savings in the chiller as well as in the selection of air handling units and other system equipment. Instead of having many chillers in a building, Plate Heat Exchanger s can be placed on several floors as pressure breakers. This has a positive effect on building design:
• They are very compact and only require normal floor height, i.e. <3 m/10 ft, and only a third of the floor space of a chiller with identical capacity. This makes them easy to fit in, even in buildings with limited space.
• They do not cause any vibrations or noise. This will save money for the owner as the rest of the floor can be rented out without the tenants being disturbed.
• They do not normally need any maintenance attention, apart from a planned maintenance consisting of a gasket replacement approximately every 10–12 years.